Glossary · Ex i

What is Intrinsic safety (Ex i)?

A protection concept that limits the electrical energy in a circuit so it cannot produce an igniting spark or heat, even under fault conditions.

Defined in IEC 60079-11 with levels ia (two faults, suits Zone 0), ib (one fault, Zone 1) and ic (Zone 2). Very common for 4-20 mA instruments.

It needs a barrier or isolator in the safe area, and a check that the cable and device capacitance and inductance stay within the permitted limits.

Related terms

4-20 mA signal
The most widely used analogue signal in industrial measurement: 4 mA is the bottom of the range and 20 mA the top, and current, unlike voltage, is not affected by cable length.
Equipment Protection Level (EPL)
The equipment protection level states how safe a device is as an ignition source, and maps directly to the zones where it may be used.
Flameproof protection (Ex d)
A protection concept that lets an explosion happen inside the enclosure, which withstands it and cools the escaping flame through its gaps so the surrounding atmosphere does not ignite.

All terms