4-20 mA calculator: scaling and loop power budget

Scale current to engineering units and check the loop voltage budget.

Scaling

5.000 bar
50.0% of spanWithin measuring range (NAMUR NE43)

Loop voltage budget

Voltage at transmitter at 22 mA
17.62 V
Max allowed loop resistance
614 Ω
Loop is adequate

Linear scaling: PV = LRV + (URV − LRV) × (mA − 4) / 16. NAMUR NE43: measurement between 3.8 and 20.5 mA; failure at ≤3.6 mA or ≥21 mA.

The loop budget is checked at 22 mA (worst case): voltage at the transmitter = supply − barrier drop − 0.022 × (load + cable). It must stay above the transmitter lift-off voltage.

FAQ

How do I convert 12 mA to engineering units?

12 mA is exactly mid-range: a 0–10 bar transmitter reads 5 bar. The formula is value = LRV + span × (mA − 4) / 16.

Why is the budget checked at 22 mA?

It is the worst case: at saturation or the high failure signal the voltage drop across the resistances peaks, and the transmitter must stay above its lift-off voltage.

What does a 3.6 mA reading mean?

Under NAMUR NE43, 3.6 mA or less means the transmitter is signalling a failure, not a real measurement.