Final project: a complete tank station with a state machine and alarms
The capstone that pulls the whole course together: start permissives, a CASE state machine with step timeouts, timers and a counter, a filtered level, an acknowledged alarm and a fault state.
What we are building
A station that runs batch after batch: fill the tank to a setpoint, hold for a settling period, drain to a low limit, log a batch, repeat. It stops safely on anything odd and raises an alarm that a human has to acknowledge. That is the skeleton of every real batch station, however large.
Decision 1: permissives before motion
No first step until the conditions are sound. Collect them into one named variable:
Permissive := NOT (LSH AND LSL) AND LevelF <= 99.0;LSH AND LSL together is physically impossible, so it means a failed switch or a broken wire. One named condition beats seven conditions repeated in seven places: you read it in the watch table and know immediately why the station did not start.
Decision 2: the filtered level, not the raw one
A level measurement jitters, and any comparison against the raw value jitters with it. A one-line exponential filter:
LevelF := LevelF + 0.20 * (Level - LevelF);The 0.20 means "take a fifth of the new reading", a reasonable trade between quiet and responsive. We copy the raw value once on the first scan, otherwise the filter starts at zero and we wait while it climbs.
Decision 3: a state machine, not a chain of conditions
Five states, each knowing its outputs and its one exit condition:
Step | State | Outputs | Exit |
|---|---|---|---|
0 | Idle | all off | run command and permissives healthy |
1 | Filling | pump | level ≥ 85% |
2 | Settling | all off | 3 seconds |
3 | Draining | valve | level ≤ 12% or LSL |
4 | Complete | all off | one scan, counts the batch |
9 | Fault | all off | operator acknowledge |
Two rules keep a state machine clean: an output is set in exactly one place, and each state has one clear exit. Fault is 9, well away from the sequence numbers, so the number alone tells you that you are outside the normal flow.
Decision 4: a timeout on every moving step
A step waiting on a physical event must wait with a limit. If fill is commanded and the level has not risen in 60 seconds, the pump has failed, a valve is shut, or the source is empty. Without a timeout the program waits forever while the pump runs dry.
One timer serves both moving steps, reset on any step change by comparing the current step with the previous one.
Decision 5: an ISA-18.2 style alarm
An alarm is not HiAlm := Level > 90. ISA-18.2 separates the process condition from the alarm state, and the practical consequence is this: the alarm stays visible until a human acknowledges it, even if the level has long since returned to normal. A deadband stops it chattering around the threshold:
- Raised above 90% or on
LSH. - Cleared only below 85% and after acknowledge.
- The lamp flashes while unacknowledged, and goes steady once acknowledged but still active.
The lab panel has only two buttons, so a START press doubles as acknowledge whenever there is an unacknowledged alarm or a fault. On a real station that is a pushbutton or a click on the HMI.
Decision 6: edges, not levels
Start, acknowledge and batch counting are all events, and an event is read on a rising edge. Without R_TRIG the batch counter would log twenty batches a second because the completion condition is true every scan. That is also why state 4 exists: a state that lives for one scan, counts, and leaves.
Decision 7: who stops what
Stop returns the machine to idle in an orderly way. A fault goes to state 9, drops everything, and stays there. The difference is deliberate: a stop is an operator request, a fault is a condition that needs a person to understand what happened before anything restarts.
How to read the program
The lab program under this lesson is laid out in eight sections, in this order: setpoints, filter, events and edges, alarm, fault detection, state machine, step timing, outputs. The order is not decoration. Everything that reads comes before everything that decides, and everything that decides comes before everything that writes. Follow it in every program you write from here on.
Try it in the lab
The lab runs in your browser: an ST editor, a virtual process that suits the lesson, the same program as a live ladder diagram, a watch table, and export to Siemens SCL.
What to try
- Press START and follow Step: 1 fill, 2 settle, 3 drain, 4 complete, then 1 again.
- Watch Batches.CV rise with each batch; after 3 the station stops and the lamp lights. Press START for a new shift.
- Press STOP in any step: it returns to 0 at once.
- Change 80.0 to 95.0: the level reaches 90%, LSH trips and the alarm lights. That is the independent safety layer.
Terms in this lesson
People find this lesson by searching
complete plc project exampleCASE state machine structured texttank control plc programstep timeout plc sequenceISA 18.2 alarm acknowledgebatch counter plcstructured text capstone project
Course outline
- 01What is Structured Text, and when to use it instead of ladder
- 02How a PLC runs your code: the scan cycle and the process image
- 03Program structure: POUs, PROGRAM, FUNCTION and FUNCTION_BLOCK
- 04Your first program: starting a pump with seal-in logic
- 05Data types: BOOL, INT, REAL, TIME and the rest
- 06Declaring variables: VAR, VAR_INPUT and RETAIN
- 07Literals and constants: 16#FF, 2#1010 and T#5s
- 08Type conversion and scaling a 4-20 mA signal
- 09Assignment and arithmetic in ST: := and operator precedence
- 10Boolean logic, comparisons and bit operations
- 11Standard functions: ABS, SQRT, MIN, MAX, LIMIT, SEL, MUX
- 12IF, ELSIF and ELSE: the rules and when to avoid them
- 13The CASE statement and your first state machine
- 14The FOR loop and the watchdog
- 15WHILE, REPEAT, EXIT, CONTINUE and RETURN
- 16Edge detection: R_TRIG, F_TRIG and the "it fired every scan" bug
- 17Timers: TON, TOF and TP
- 18Counters: CTU, CTD and CTUD
- 19SR and RS flip-flops: which one wins
- 20Writing your own function
- 21Writing a function block
- 22Arrays in Structured Text
- 23Structs and enumerations
- 24References and pointers
- 25The state machine pattern: a batch sequence that cannot get stuck
- 26Alarm management to ISA-18.2: delay, deadband, latch, acknowledge, first-out
- 27Analogue signal processing: counts to engineering units, NE43 and filtering
- 28Closed-loop control in ST: hysteresis first, then a practical PID
- 29Motors and valves in practice: permissives, feedback and travel time
- 30The same ST on every platform: SCL, Studio 5000, CODESYS, TwinCAT
- 31Testing and debugging ST: the watch table, forcing and simulation
- 32An ST style guide: naming, comments, constants and version control
- 33Final project: a complete tank station with a state machine and alarms
- 3420 interview questions on ST and PLC programming, with answers